your location:Home - Products - Substation
YB □ -12 / 0.4 high voltage/ low voltage prefabricated substation
medium voltage recloser, circuit breaker, RMU, switchgear manufacturer - New Concept Electric
  • YB□-12/0.4 high voltage / low voltage prefabricated substation is based on the on-site service and operation experience of prefabricated substation for many years, and it absorbs foreign advanced technology and design concept. A new product designed and manufactured for the distribution network. It has excellent performances such as reliable power supply, reasonable structure, fast installation, flexibility, convenient operation, small size and beautiful appearance. It is mainly used in urban and rural power grids of 10/11/12kV, and is also suitable for industrial and mining enterprises, airports, stations, ports, highways, subways and other public places.


    Use of the environment

    DescriptionUnitEnvironmental values
    Ambient air temperatureMaximum temperature+50
    Minimum temperature-40
    Maximum daily temperature differenceK30
    Altitudem≤3000
    Solar radiation intensityW / cm20.1
    Pollution Level
    Icing thicknessmm10
    humidityDaily average relative humidity%≤100
    Monthly average relative humidity≤95
    The ability to withstand earthquakesdegree≤8

    Note: The list of environmental parameters beyond the scope of the requirements, please contact me.

    20190814160005117.jpg@!w800

    20190814160002218.jpg@!w800

    The main technical parameters

    DescriptionUnitParameter
    High-voltage unitRated voltagekV12
    Rated frequencyHz50/60
    1min rated power frequency withstand voltage (earth, white / fracture)kV42/48
    Lightning impulse withstand voltage (earth, white / fracture)kV75/85
    Current RatingA630
    Rated short time withstand currentkA20
    Rated peak withstand currentkA50
    A low-pressure unitRated voltageV400
    Main circuit rated currentA100 to 2500
    Rated short time withstand current (ground loop)kA12.5
    Rated peak withstand current (ground loops)kV31.5
    Feeder loop currentA10 to 630
    Feeder Looproad1 to 12
    Compensation capacitykVarTransformer capacity by 20% to 40%
    Transformer unitRated CapacitykVA30 to 1250
    Impedance voltage%4/6
    Tapping range
    ± 2X2.5%, ± 5%
    Connection Arrangement
    Dyn11, Yyn0
    CabinetEnclosure rating
    IP33D
    Sound level leveldBmeet specs

    Note: If technical parameters exceed your scopes, please contact us.


  • The main technical parameters

    DescriptionUnitParameter
    High-voltage unitRated voltagekV12
    Rated frequencyHz50/60
    1min rated power frequency withstand voltage (earth, white / fracture)kV42/48
    Lightning impulse withstand voltage (earth, white / fracture)kV75/85
    Current RatingA630
    Rated short time withstand currentkA20
    Rated peak withstand currentkA50
    A low-pressure unitRated voltageV400
    Main circuit rated currentA100 to 2500
    Rated short time withstand current (ground loop)kA12.5
    Rated peak withstand current (ground loops)kV31.5
    Feeder loop currentA10 to 630
    Feeder Looproad1 to 12
    Compensation capacitykVarTransformer capacity by 20% to 40%
    Transformer unitRated CapacitykVA30 to 1250
    Impedance voltage%4/6
    Tapping range
    ± 2X2.5%, ± 5%
    Connection Arrangement
    Dyn11, Yyn0
    CabinetEnclosure rating
    IP33D
    Sound level leveldBmeet specs

    Note: If technical parameters beyond your scopes, please contact me


  • Feature

    Compact structure, small volume, small footprint, easy to transport,  triangle and abreast assembly types.
    The shell is designed and produced by using domestic advanced technology and selecting new materials. It has the characteristics of strong, heat-insulating, dust-proof, moisture-proof, and anti-small animals. The shell can be made of steel, composite, non-metal and other materials.
    It adopts labyrinth plate structure, which not only has beautiful appearance, convenient disassembly, but also has good thermal performance of ventilation fan.

    Fully insulated and fully protected design. The frame structure of the box is made of channel steel and angle steel. It has sufficient mechanical strength. The inner and outer surfaces of the parts of the box are treated with anti-corrosion coating to ensure no corrosion for a long time and a durable protective layer. The top cover of the cabinet is double-layered to prevent heat radiation to increase the indoor temperature.

    The protection performance is perfect, the operation is convenient, and the high and low pressure sides can be metered.

    All the doors of the cabinet do not have the lighting device for opening and closing the automatic switch.

    All the doors of the cabinet are opened outwards, the opening angle is greater than 90°, and there are positioning devices. The door is equipped with handles, hidden doors, and is equipped with locks that protect against rain, rust and blockage.

    Note: For additional functional requirements, please contact us.